本文通过对我国某电力系统的研究指出:重合时间延长或缩短何种对系统永久故障下动态稳定性更为有利的问题,主要取决系统跳开故障相线路后非全相运行的静态稳定储备系数的大小。并进一步提出了以发端系统等值机与受端系统等值机的相对角度δ_(12)对时间的导数(切除故障相后)大于零或小于零作为重合时间应该缩短或延长的判别准则。这个问题的研究对提高我国高压输电系统的输送能力是有一定意义的。
In this paper, a study on a power system in our country shows that the problem of whether the coincidence time is prolonged or shortened is more favorable to the dynamic stability under the permanent fault of the system depends mainly on the static stable reserve coefficient the size of. Furthermore, the criterion of whether the relative angle δ_ (12) of the originator system and the equivalent system of the receiving end system to time (after the removal of the fault) is more than zero or less than zero should be shortened or extended as the coincidence time. The research on this issue is of certain significance to improve the transmission capacity of high voltage transmission system in our country.