本文针多联式空调系统在实际运行时是否节能的问题,基于不同建筑面积的4个办公建筑模型,分析了数码涡旋多联式空调系统、定风量全空气系统和风机盘管加新风系统在实际运行时,室外工况、区域负荷和运行时间3个因素对其运行能耗的影响,并分析了能耗差异的原因。结果表明,与定风量全空气系统和风机盘管加新风系统相比,数码涡旋多联式空调系统在变工况时的调节特性最好;在变负荷工况下,是否存在定风量全空气系统或风机盘管加新风系统比数码涡旋多联式空调系统节能的空调开启率分界点及其分界点值的大小取决于建筑负荷与空调系统部分负荷性能之间的匹配;与定风量全空气系统相比,数码涡旋多联式空调系统的室内机个性化调节的特性使其在房间的空调运行时间参差时更为节能。
In this paper, multi-connected air-conditioning system in the actual operation of the energy-saving issues, based on different building area of the four office building models, analysis of the digital scroll multi-type air conditioning system, the constant air volume air system and fan coil plus fresh air system In the actual operation, the outdoor conditions, the regional load and the running time of the three factors on the operation of energy consumption, and analyzes the reasons for the differences in energy consumption. The results show that compared with the constant air volume air system and the fan coil plus fresh air system, the digital vortex multi-connected air conditioning system has the best adjustment performance under varying working conditions. Under variable load conditions, Air system or fan coil plus fresh air system than the digital scroll multi-air-conditioning system energy-saving air-conditioning start-up rate cut-off point and the value of the size of the demarcation point depends on the building load and air conditioning system load performance between the part of the match; Compared with the whole air system, the personalized regulation of the indoor unit of the digital scroll multi-type air conditioning system makes it more energy-saving when the running time of the air conditioner in the room is variable.