Research on energy saving of centralized air-conditioning system based on mathematical model

来源 :现代盐化工 | 被引量 : 0次 | 上传用户:lkstudybitcc2008
下载到本地 , 更方便阅读
声明 : 本文档内容版权归属内容提供方 , 如果您对本文有版权争议 , 可与客服联系进行内容授权或下架
论文部分内容阅读
  Abstract:Centralized air-conditioning is a multi-component, non-linear, large delay system, all of its air processing equipment are concentrated in the air-conditioning room, it is difficult to model and control the system. At present, there are many researches on energy saving of central air-conditioning system, but most of the studies do not take the whole system as the starting point to establish an effective model. In this paper, the mathematical models of the components of the central air conditioning system are established and simulated, and the influence of the flow rate (air volume) of the refrigerated water, cooling tower and air treatment box on the energy saving effect of the air conditioning system is discussed one by one.
  Key words:centralized air conditioning system; mathematical model; flow; energy saving
  1    Introduction
  With the development of science and technology and the improvement of peopleundefineds living standards, air conditioning has become an irreplaceable part of peopleundefineds work and life. Among them, the equipment of centralized air conditioning system is numerous, the structure is complex, and there are many factors affecting its energy consumption.And the centralized air-conditioning system is composed of various equipment according to certain heat and power characteristics, the components are interdependent, and the characteristics of large hysteresis, multi-variable and random interference are not easy to be controlled[1].
  For the above-mentioned characteristics of the central air-conditioning system, how to achieve the energy-saving effect of the whole system by changing the control method of the air-conditioning system has become the key research direction of the experts at home and abroad.Chan KT and others carried out variable flow control of frozen water in central air-conditioning system, and explored the energy-saving potential of variable frozen water flow[2];Jin and so on can improve the energy-saving performance of the system by controlling the water supply temperature of the frozen water and the water supply pressure of the frozen water pump[3]; The model of centrifugal chillers was established by Lee et al[4]. The influence of variable flow rate of frozen water on the operation performance of air conditioning system was studied[5];According to the year-round operation data of the air conditioning system, Wang et al analyzed the influence of the frequency conversion control of the frozen water pump and the cooling pump on the energy saving of the system[6]; Hu Lei and others reformed the air-conditioning chillers and studied the energy-saving effect of variable flow rate of cooling water[7]. The effects of variable flow rate (air volume) on the performance of air-conditioning system are discussed one by one in the research of frozen water pump, cooling pump and air treatment box.   In this paper, the mathematical model of air-conditioning system is established and verified. Based on the established air-conditioning system model, the freezing water pump and cooling tower are studied one by one. The influence of variable flow rate (air volume) of air-conditioning treatment box on the energy-saving effect of the system.
  2    Composition and principle of centralized air conditioning system
  Centralized air conditioning system means that all air treatment equipment is concentrated in air conditioning room, there are water chillers and air treatment equipment, all kinds of terminal systems and so on. The main components of the central air conditioning system are: cooling pump, frozen water pump, chiller, cooling tower, air processor, etc. The central air-conditioning system connects the air outlet through the air duct or hot pipe, and the main engine sends the heating and cooling to different areas to achieve the purpose of regulating the indoor air[8].
  3    Establishment of each part model of the air-conditioning system
  Formula(1)to formula(3): mr refrigerant flow rate, kg/s; ξ as compressor gas transfer coefficient; Vth theoretical compressor gas delivery capacity, m3/kg; v refrigerant specific capacity at suction port, refrigerant exhaust enthalpy value at m3/kg; h2 for evaporation pressure, Pa; Pe is the variable exponent of the compression process; Pth is the actual power of the compressor, kW.
  Evaporator and condenser model: evaporator is similar to the condenser in principle, and the formula is as follows:
  In formula: the heat transfer coefficient of refrigerant side single phase zone is all based on standard Dittus-Boele formula:
  The heat transfer coefficients in the two-phase region on the refrigerant side are as follows:
  The heat transfer coefficient of the frozen water side is as follows:
  Formula: mwe for the flow rate of frozen water, kg/s; Cpw is the specific heat capacity of water, and kJ/kg; twie、twoe is the inlet, outlet temperature and ℃ of frozen water, respectively; h6 it is the enthalpy of refrigerant throttling, kJ/kg; Qe is refrigeration capacity, and kW; Ke is the refrigeration capacity. For the total heat transfer coefficient of the evaporator, W/(m2·K); Ae is the evaporator area, m2; ΔTe the average temperature difference in heat transfer, K; λe is the thermal conductivity of the refrigerant, W/(m·K);  λw is the thermal conductivity of the water, W/(m·K); do is the external diameter of evaporator tube, m; di is the inner diameter of evaporator tube, m.   Throttle model: refrigerant flow formula is:
  In: Cv for flow coefficient; Av for valve flow area, m2; ρv for refrigerant liquid density, kg/m3; Pvi、Pvofor throttle valve inlet and outlet pressure, Pa.
  (1)Air treatment box model:
  Qcoil is for air treatment box heat exchange, kW; twic, twoc is refrigerated water inlet / outlet air treatment box temperature, mac is air conditioning box air volume, m3/h, hair, haoc are air in and out air treatment box enthalpy, kJ/kg; ε1, ε2 are the coefficient of heat exchange efficiency and contact coefficient, tgi, tgo are the dry bulb temperature of air in and out of the air treatment box, tsi, tso the wet bulb temperature of air in and out of the air treatment box, ℃, NTU is the number of heat transfer units of the air treatment box, respectively, γ is the temperature of the dry bulb of air in and out of the air treatment box. αo is for water equivalent ratio,W/(m2·k); Acoil for air side surface heat transfer coefficient; air side heat transfer area, m2.
  Cooling tower model:
  mw·t is for the cooling tower water mass flow, kg/s; dz is the vertical length of the cooling tower packing, ma·t is the cooling tower air mass flow rate, kg/s; X is the air vapor mass component in the cooling tower, tw·t is the cooling water temperature is the cooling water temperature, ha·t the cooling water temperature is the cooling water temperature, kJ/kg; A is the cooling water temperature is the cooling water temperature. Fz is the enthalpy of the air in the cooling tower, m2; βt is the saturated air moisture content corresponding to the water temperature, and the moisture content of the saturated air corresponding to the water temperature. W/(m2?℃); Cpv·a for constant pressure specific heat with air temperature as qualitative temperature. kJ/ (kg. ℃); at air temperature as qualitative temperature, kJ/kg; ta·t for water. For air temperature, ℃.
  Pump and fan model: pump and the fan follow the similar law:
  In this model, V is the flow rate of pump or fan, m2/s; H is head, m; ρ is water or air density is water or air density, kg/m3;P is power, kW; ηVFD is frequency converter, motor efficiency is motor efficiency, pump efficiency is pump efficiency, ηm is frequency converter. Subscript m indicates rated condition.
  4    System simulation and results
  In order to verify the accuracy of the model, the frozen water flow rate(0.5%)was tested in this paper(0.5~0.8 kg/s), cooling water flow rate(0.6~1 kg/s), air treatment box(600~1 200 m3/h)was measured to measure the cooling water, the inlet and outlet temperature of cooling water, the air inlet and outlet status of air treatment box and cooling tower, and the energy consumption of air conditioning units. Water pump energy consumption and fan energy consumption are compared with the predicted results under the same working conditions to verify the accuracy of the model.   When the flow rate of the chilled water pump is changed, the flow rate is set to 50%,62.5%,75%, 87.5% and 100% of the rated flow, respectively. And the flow rate of the cooling water and the air volume of the air treatment box are kept constant; and when the flow rate of the cooling water pump is changed, the flow rate is respectively set to be 63. 6%, 72.7%, 81.8%, 90.9% and 100%. When the air volume of the air treatment box is changed, the air volume is set to 50% of the rated air volume, and 62. 5%,75%,87. 5% and 100%. The flow of chilled water and cooling water is kept constant.
  Fig3 is a comparison of the experimental and simulation results of the cooling capacity of the water chilling unit under different working conditions. It can be seen from the figure that the maximum cooling capacity is within 5%. Fig4 shows the comparison between the experimental value of the performance coefficient(COP value)of the unit and the simulation value under different working conditions, and the maximum deviation of the COP value is within 10%, and the accuracy of the system model is verified.
  In this paper, the dry bulb temperature of the air conditioning system is set to 26 ℃, the wet bulb temperature is 18 ℃, the inlet dry bulb temperature of the cooling tower is 35 ℃, the wet bulb temperature is 26 ℃, and the flow rate of the frozen pump is 0.8 kg/s. The flow rate of the cooling pump is 1 kg/s, the air volume of the air treatment box is 1 200 m3/h, and the fan flow rate of the cooling tower is 5 200 m3/h, which is set to 100% and 87% of the rated flow, respectively 5%, 75%, 62. 5% and 50%.
  Fig5 is the effect of variable cooling water flow rate, variable air treatment box air volume and cooling tower air volume on the cooling capacity of the air conditioning system. The change rate of refrigerating capacity in the diagram is the ratio of the change of refrigerating capacity to the refrigerating capacity at rated flow rate when the above parameters are reduced from 100% to 50%.
  5    Summary
  As can be seen from figure 5, the cooling capacity of the system is reduced by about 6.5% and 2.3% respectively when the cooling water, the cooling water flow, the air flow rate of the air treatment box and the cooling tower are reduced from 100% to 50% of the rated flow, respectively, and the cooling capacity of the system is reduced by 6.5% and 2.3%, respectively. 11.8% and 0.3%. Because the change of condensation temperature has no direct effect on the heat transfer process of the evaporator and has little effect on the cooling capacity of the air conditioning system, the influence of the variable cooling water flow rate and the variable cooling tower air volume on the cooling capacity is relatively small. On the whole, the air volume of the variable air treatment box has the greatest influence on the cooling capacity, followed by the variable freezing water, the cooling water flow rate, and the variable cooling tower air volume has the least effect on the refrigerating capacity.   [Reference]
  [1]YU F W,CHAN K T.Improved energy performance of air cooled centrifugal chillers with variable chilled water flow[J].Energy Conversion&Management,2008,49(6):1595-1611.
  [2]JIN X,DU Z,XIAO X.Energy evaluation of optimal control strategies for central VWV chiller systems[J].Applied Thermal Engineering,2007,27(5/6):934-941.
  [3]LEE T S,LIAO K Y,LU W C.Evaluation of the suitability of empirically-based models for predicting energy performance of centrifugal water chillers with variable chilled water flou[J].Applied Energy,2011,93(5):583-595.
  [4]WANG F J,CHANG T B,CHEN M T.Energy Conservation for Chiller Plants by Implementation of Variable Speed Driven Approach in an Industrial Building[J].Energy Procedia,2014,6(1):2537-2540.
  [5]BRADLEY B,SCHWEDLER M.Variable primary flow in chilled-water systems[J].Heating piping air Conditioning,2003,3(75):37-45.
  [6]BRANDON F.LACHNER.The use of water as refrigerant:impact of cycle modification on commercial feasibility[D].University of Wisconsin,School of Mechanical Engineering,2004.
  [7]SAIDUR R,HASANUZZAMAN M,MAHLIA T M,et al.Chillers energy consumption,energy savings and emission analysis in an institutional buildings[J].Energy,2011,36(8):5233-5238.
  [8]MENG QINGLONG,YAN XIUYING,REN QINGCHANG.Global optimal control of variable air volume air-conditioning system with iterative learning:an experimental case study[J].Journal of Zhejiang University-Science a,2015,16(4):302-315.
其他文献
摘 要:为了减少工地施工人员伤亡,设计将无人机技术初步应用到工地外墙粉刷上,该装置由无人机、胶皮管、可旋转式喷头、触碰感应系统、高清摄像头、基站等部件构成,将无人机与便携式喷涂器结合,形成外墙喷涂无人机,改良已有的喷涂机,将喷头变为可调控制喷头,通过遥控器的控制,让喷头在上下60°之间来回转动,让其能够喷涂更灵活,适应各种复杂墙面墙角,不用二次施工,喷涂无高度限制,任意楼层喷涂,降低工地施工伤亡
期刊
摘 要:“第三者”是指在行为人进行正当防卫过程中,没有实施或参加不法侵害的其他人。分析了对于防卫行为误伤第三者情形的性质应当如何认定,刑法学界存在诸多学说,包括正当防卫论、紧急避险论、假想防卫论等,在这些学说中区分论更为合理、全面,即在法益侵犯原则和责任主义原则上,从违法性和有责性层面出发,根据具体案情区别处理,从而认定这种情形成立故意犯罪、过失犯罪、意外事件或者紧急避险。  关键词:正当防卫;不
期刊
摘 要:随着“互联网+”时代的到来,“互联网+微课”技术也逐渐被应用在高职教学中。本文以“自动化生产线安装与调试”课程为例,探讨了“互联网+”微课对高职教学的影响。本文分别从微课对教学方法的促进、微课对学生学习态度的影响、“互联网+”微课对课程教学组织与实施的影响、“互联网+”微课对教学评价的影响4个方面进行阐述,得到“互联网+”微课符合当代高职学生教学需要的结论。“互联网+”微课在教学中的应用使
期刊
摘 要:文章通过对应用技术型民办高校会计人才培养目标和企业会计人才需求特点进行分析,以重庆某高校调研数据为例,分析应用技术型民办高校会计学专业实践教学改革必要性,并提出“实践先导型”实践教学方法改革的实施要点,为会计学专业实践教学改革提供新思路。  关键词:应用技术型大学;民办高校;会计学专业;实践教学;实践先导型  1 应用技术型民办高校会计人才培养目标  人才培养目标是高校人才培养的基本准则
期刊
Abstract:Traditionally, most land use projects do not consider the impact of environmental pollution. However, with the worsening of the natural environment, environmental cost cannot be ignored. Ther
期刊
摘 要:在企业的日常运营管理中营运资本管理占据着重要地位,如果把企业看作一个人,那么营运资金就是人体中流动的血液。在传统的基于要素视角的营运资金管理分析的基础上,结合渠道理论对美的电器的营运资金管理现状进行分析,发现美的电器的营运资金管理现状的不足之处,并提出改善建议,希望对其他企业有一定的借鉴意义。  关键词:营运资本;营运资金管理;美的电器  1 相关理论  1.1 传统营运资金管理理论 
期刊
摘 要:青年筑梦促读公益组织本着为贫困地区小学的孩子提供持续的、高质量的阅读项目的初心,从图书利用层面强化扶贫导向。通过改进图书的采购标准、图书的更新标准、图书的高效利用、老师学生的相关培训等主要工作,建立贫困地区小学图书高效利用一体化机制,从而改善担当者行动图书角利用方式,加强小学生的高质量知识储备与利用能力,并不断提升学校小升初的质量。  关键词:高质量阅读;贫困地区小学;班班有个图书角;扶
期刊
摘 要:內部控制的重大缺陷如果不及时加以修复,经过层层放大后极有可能给企业带来巨大影响,甚至会造成企业的灭亡。海润光伏自2016年起到2018年,3年间的财务报告都被出具了“无法表示意见”的审计意见,其股价自此一路下滑,截至目前已被停止上市。对海润光伏作出案例分析,首先,以其财务报告首次被出具无法表示审计意见当年(2016年度)的内部控制审计报告为出发点,进而剖析其内部控制缺陷,并在此基础上对其
期刊
摘 要:信号在企业中扮演着很重要的角色,在现实生活中投资者往往只能从这么几方面来了解一个上市公司:股利政策、资本结构、相关的企业报道以及发布的企业财报。通过信号传递理论来分析格力影响股价和企业价值的因素,探讨企业发出的不同信号中传递了怎样的信息,这些信息对于投资者而言又会做出怎样的反应,从而对企业价值产生的影响,研究得出企业的管理者完全可以利用合理的信号来向投资者传达利好或者利空的信息来进一步影
期刊
摘 要:以运城职业技术学院电子信息工程系2016级在校生为研究对象,以“C语言程序设计”课程为例,实行24字教学模式—阅读感悟、自学检测、合作交流、展示点评、分层训练、拓展延伸,将其作为“第二课堂”的开展内容,研究其与高职学生的“三大素养”培育间的关系,为高职学生的培养提供导向。  关键词:第二课堂;三大素养;高职学生  1 研究背景  《国务院关于印发国家职业教育改革实施方案的通知》(国发〔
期刊