压缩空气系统设计

来源 :商品与质量·理论研究 | 被引量 : 0次 | 上传用户:bright545454
下载到本地 , 更方便阅读
声明 : 本文档内容版权归属内容提供方 , 如果您对本文有版权争议 , 可与客服联系进行内容授权或下架
论文部分内容阅读
  摘要:一个好的压缩空气系统设计对于半导体芯片厂是非常重要的。这篇论文主要是介绍压缩空气系统的设计思路。 本文主要讲述一下内容: 总体目标、气体要求、扩充策略、维护保养、空气流通、气体品质与压力、系统中的压力损失、系统框架等。
  关键字:压缩空气;压力;容量;质量
  
  Abstract: A well designed compressed air system is very important for a semiconductor wafer Fab operation. This paper gave the designer of compressed air system design. The following topics covered in this paper: Overall objective, Air demand, Expansion strategy, Maintenance considerations, Ventilation, Air quality, Air pressure, Pressure Loss in Air System, Information needed by supplier, Air Receiver Sizing, System Layout. Even you are designing a new compressed air system or you want to get your exist system expanded, you will find this paper is helpful for your project.
  Key Words: Air compressor; Pressure; Capacity; Quality
  Compressed Air System Design
  I Overall objective of compressed air system design
  Meet average air demand
  Meet peak air demand
  Provides the quality of air needed for the application
  Provides at least the minimum required air pressure
  Provide capability for future expansion
  Provide capability for easy maintenance
  Provides sufficient ventilation
  Keep the project cost within budget
  Minimize operation cost
  II Air demand
  Air demand can be determined from flow measurements or by observation of exist compressor load factors in an existing system. An air survey can be done on an existing system or for a proposed system to determine air demand. If an existing system has the compressors running at 100% use factor and is still not maintaining design pressure, PLANT REQUIRED CAPACITY CHART located in this section can be used to determine how much additional capacity is required to bring the pressure back up to the design point.
  For example: if existing plant capacity is 2000 scfm, existing pressure is 90 psi, but the required pressure is 110 psi. We assume load factor is 100%,the additional capacity required for each 1000 scfm (existing) can be
  200scfm€? =400scfm
  Determined in the chart : 200scfm/1000scfm. So the total additional capacity is :Total required capacity is 2400 scfm, as shown in the above chart.
  III Expansion strategy
  One approach to future expansion requirements is to oversize the existing system. This may take the form of one or more compressors designed to run at less than full load to meet present demand allowing for increased air production in the future. It may also take the form of installing one or more additional compressors the are on standby until needed. Another approach is to design the compressor room and piping system such that additional compression equipments can be added later.
  IV Maintenance considerations
  All compressors require routine preventive maintenance and nearly all compressors eventually experience an unexpected outage. If the cost to an outage is extreme, it is wise to consider a stand-by compressor in the system. When maintenance is required, it is necessary to have sufficient room to work on the compressor system. Make sure there is enough clearance around and above the components to facilitate maintenance. Minimum clearances can be obtained from the equipment supplier for specific item, Overhead lifting capability is useful.
  If the compressor intake is located indoors, sufficient air must be available to pass through the intake filter and into the compressor. This need for ventilation, however, is minor compared to the ventilation required for removal of heat. It is generally true that:
  □An air cooled compressor rejects about 42.4 BTU/Min per BHP to the air around itself.
  □A water cooled compressor rejects between 13% and 30% of that amount (the rest is rejected to the cooling water). Based on a 330 BHP compressor:
  Get specific heat rejection data from the equipment manufacturer in order to determine ventilation requirement.
  The specific heat of air at 14.7 psia, 60Deg F is 0.018336 BUT/CUBIC FT-DEG F. In order to ventilate a room for a 330 BHP air cooled unit allowing a 10 DEG F temperature rise in the cooling air would require the following;
  (330 X 42.4 BTU/MIN)X(CUBIC FT-DEG F/0.018336 BTU)/(10 DEG F)=76,309 CFM OF VENTILATING AIR
  V Air quality / pressure
  The quality of is determined by it's intended use. Dew point requirements can be addressed with aftercoolers and dryers. Oil content can be addressed with oil free compressors or filtration. Particulate matter can be addressed with piping materials and filtration. Refer to the manufacturer's catalog to select the aftercooler, dryer and filter.
  Determine air pressure requirements at the point of use. Most air pressure requirements are satisfied by selection of the proper compressor design pressure and a properly designed piping system. Low pressure requirements are often satisfied from the plant air system through a pressure regulator. When constant pressure is required at the point of use and normal system pressure fluctuations are a problem, a point of use pressure regulator is generally the solution. In this last case system pressure must be designed to always be above the desired pressure after the regulator.
  VI Pressure loss in air systems
  Determine air pressure requirements at the point of use. Most air pressure requirements are satisfied by selection of the proper compressor design pressure and a properly designed piping system. Low pressure requirements are often satisfied from the plant air system through a pressure regulator, when constant pressure is required at the point of use and normal system pressure fluctuations are problem, a point of use pressure regulator is generally the solution. In this last case system pressure must be designed to always be above the desired pressure after the regulator.
  Pressure Loss in Air Systems
  Pressure drops for components such as aftercoolers, dryers and filters should be obtained from the manufacturer. The expected pressure drop through the piping system can be estimated using the pressure loss tables and equivalent length table.
  VII Information needed by supplier
  The supplier should be given the following design conditions:
  Barometer=psia
  Inlet air temperature=Deg F
  Relative humidity=%
  Cooling water temperature=Deg F (if applicable)
  Discharge pressure=psig
  Air Flow=ICFM or ACFM or SCFM
  Definitions:
  ICFM - Inlet Cubic Feet per Minute. This is a measurement of the air entering the compressor.
  ACFM - actual Cubic Feet per Minute. This is measurement of actual air delivered, referred to inlet conditions.
  SCFM-Standard Cubic Feet per Minute Delivered. This is a measure of delivered capacity rapacity referred to some standard set of conditions. The most common set of standard conditions are 14.7psia, 60 Deg F and 0% relative humidity.
  The supplier should also be given the minimum and maximum inlet air temperatures. If it is a water cooled application, Minimum and maximum cooling water temperatures should also be stated.
  VIII Air Receiver Sizing
  The air receiver size can be determined based on manufacturer's recommendation or system requirements.
  The following formula can be used to size a tank based on system needs.
  V: Receiver Capacity, in Cubic Feet
  T: Compressor off line time prior to loading, in Minutes
  P2: Final Receiver Pressure when the compressor just be off ling, in psig
  P1: Initial Receiver Pressure when the compressor starts, in psig
  C: Actual Compressor Delivery, ACFM
  Pa: Atmospheric pressure, PSIA
  IX System Layout
  The following picture shows the general layout for compressed air system.
  
  作者简介:张榕,男,汉族,天津人;中级工程师,中芯国际集成电路制造(天津)有限公司,研究方向:机电/控制/洁净室。
  注:本文中所涉及到的图表、注解、公式等内容请以PDF格式阅读原文
其他文献
摘 要:据2008年底抽样调查,山东省60岁及以上老年人口有1337.28万人,位居全国第一;老年人口占全省总人口的比例为14.20%,高出全国2.2个百分点。根据山东省第六次人口普查主要数据公报,截至2010年11月1日,全省65岁及以上老年人口有942.98万人,占全省总人口的比例为9.84%。在此严峻的老龄化形势下,山东省应高度重视养老问题,根据经济社会发展实际,循序渐进地推行和建立"以居家
期刊
摘要:发展循环经济,推进节能减排,是国家的重大战略决策,是实现经济结构调整、转变增长方式的突破口和有效抓手,是贯彻落实科学发展观,构建和谐社会,促进人与自然、经济与社会和谐发展的重要途径,也是全面建设小康社会、提升区域发展水平和综合竞争力的必然选择。以循环经济理念构筑地区经济发展新模式,是社会经济和谐发展的客观需要,也是落实科学发展观的具体表现。本文试图从格尔木循环经济现状,发展中存在的主要问题入
期刊
摘要:为了规划环境影响评价的需要,已有许多指标可供选用,也有许多指标需要我们根据规划地的实际情况自己研究发现。土地规划环境影响评价指标体系建立的过程,就是要在众多的原始数据或评价信息中筛选较为灵敏、便于度量及内涵丰富的主导性指标作为评价指标的过程。  关键词:土地规划;环境影响评价;指标体系;环境效益;社会效益;以人为本;和谐社会    1引言  随着中国经济的发展,环境影响评价已经越来越受到人们
期刊
摘要:文章针对近期我国农产品市场出现的"白菜劫","芹菜劫"(农产品滞销与价格大幅波动)等农产品种植风险,从供应链的角度,运用层次分析法对农产品种植的风险进行了识别与评价,并提出了相应的风险防范措施,以便更好地保护农户与消费者的利益。  关键词:供应链;农产品种植;层次分析法;风险管理    一、引言  近期来, 农产品的安全事件层出不穷,从农业自然灾害、农产品滞销到农产品食品安全再到农产品价格的
期刊
摘要:作为低碳经济背景下的一种金融创新,碳金融提供了低碳经济所需要的各种金融工具和金融支持,也为金融体系提供了新的发展空间,碳金融成为各国发展经济的着力点。本文对我国碳金融的发展现状进行了分析,并提出了低碳经济背景下我国碳金融发展的对策建议。  关键词:低碳经济;碳金融;碳交易市场    一、引言  "低碳经济"这一概念始于西方国家。2003年2月英国在《我们的未来--创建低碳经济》白皮书中首先提
期刊
摘 要:自成立以来,地方政府融资平台对我国经济的发展做出了重要贡献,但也存在一些问题。本文首先介绍地方政府融资平台的概念与分类;其次,介绍地方政府融资平台的发展现状;最后,对规范化发展地方政府融资平台提出了自己的建议。  关键词:地方政府融资平台;财政风险;金融风险    一、引言  地方政府组建融资平台,进行基础设施建设和地方建设由来已久,但是自2008年金融危机爆发之后,地方政府融资平台才在基
期刊
摘要:随着中国商业银行的风险逐渐增加,信用风险作为商业银行面临最主要的风险也成为银行风险管理的重中之重,本文通过对中国银行业信用风险的成因分析,试图找出信用风险管理中存在的不足之处,并且最终提出完善商业银行信用风险管理的对策。  关键词:商业银行;信用风险;信用风险管理    信用风险是商业银行面临的最主要的风险,是商业银行信用风险管理的核心。信用风险又称违约风险,是源于信用活动和交易对手遭受损失
期刊
摘要:自中国加入WTO后,海外并购成为中国企业实现企业国际化战略以提高竞争力的一条重要途径,中国企业海外并购金额和并购数量也呈现出急剧增长的趋势。而在过去二十年里,中国企业海外收购案失败率高达67%,远远超过世界平均50%左右的水平。面对如此大的失败率,是什么原因让中国的企业如此钟情于海外并购?本文以TCL海外并购为例分析其海外并购的动因。研究表明,宏观背景的驱动和内部自身发展需要以及海外并购自身
期刊
摘要:本文从债务结构的期限角度,以2001年至2009年期间在上海证劵交易所首次公开发行股票的上市公司作为样本,研究其债务期限结构对盈利预测信息自愿披露的影响。根据 Logistic回归分析得出了有关结论:长期负债比率、公司规模、实际预测期间与盈利预测信息自愿披露显著相关,而流动负债比率、净资产收益率对盈利预测信息自愿性披露的影响不显著。  关键词:债务期限结构;盈利预测;信息自愿性披露    盈
期刊
自从2001年湖南省人民政府颁布《湖南省著名商标认定和保护办法》以来,衡阳市的著名商标是从无到有,商标在数量和质量上都呈上升趋势,然而,有很多商家是在削尖脑袋钻"著名商标"的光环之帽。盛名之下,其实难副,近些年来,有的著名商标已退出市场舞台,有的商标已是今不如昔,当然也也有商标正蒸蒸日上(如"金杯"、"古汉"、"天天见梳篦"已成为驰名商标)。著名商标企业所涉及的商品或服务良莠不齐,有些商家的产品质
期刊