【摘要】随着城市及农村建设的进一步发展,线路走廊越来越紧张,架空绝缘导线必然成为城市电网建设中较常用的导线之一,有助于解决裸导线路存在的诸多问题,有效的提高了线路的健康水平,增强了线路供电可靠性。但因在线路设计与施工工艺等方面存在的缺陷,导致线路在运行中发生许多故障,影响了线路的稳定运行。本文系统论述了架空绝缘导线在应用中易发生的问题,并针对存在的问题重点阐述了在运行中采取的措施。
【关键词】架空绝缘导线问题措施可靠
[Abstract] along with the further development of city and countryside construction, the line corridor became more and more nervous, overhead insulated conductor becomes one of the more commonly used wire city power grid construction, there are many problems to help guide line of bare existence, effectively improve the healthy water line level, enhance the reliability of power supply line. But due to defects in circuit design and construction technology, lead to the line has many fault in operation, affecting the stable operation of line. This paper discusses the system overhead insulated conductor prone to problems in the application, and to the problems discussed in the operation of the measures taken.
[keyword] overhead insulated conductor problem of reliable measures
中图分类号:TM245文献标识码:A 文章编号:2095-2104(2013)
1 前言
架空绝缘导线,又称架空绝缘电缆,随着社会经济的发展,架空绝缘导线是近几年在城网建设中发展起来的一种较新型线材,与普通架空裸导线相比,具有许多优点,可解决常规裸导线在运行过程中遇到的一些难题,价格又比地埋电缆造价便宜,因此,在城网与农网改造中广泛为人们所选用。但随着配电网的进一步发展和建设,线路建设越来越长。架空绝缘导线在雷雨季节时常发生雷击断线事故或导线进水氧化等事故隐患,使线路的健康水平大大降低,线路供电可靠性显著下降,提高配电线路运行检修人员的工作强度。
2 架空绝缘导线存在的问题
2.1 雷害事故多
根据濮阳郊区配网线路运行数据:2009年至2013年间,郊区配网线路共发生雷击14次,其中架空绝缘线路发生雷击9次,占郊区配电线路雷击故障的64.28%(郊区线路绝缘化率为11.89%)。因郊区配网使用架空绝缘导线时间较短,无论是新建线路还是改造线路,只考虑线路的绝缘化率的提高,与树线矛盾的问题,缺忽略了架空绝缘导线的防雷问题,对线路的安全运行造成一定的影响。
绝缘架空导线之所以容易遭受断线的原因是:当雷击绝缘导线时,绝缘导线的绝缘层会对雷电产生的电弧移动形成屏障,导致电弧移动速度较慢,使得工频电弧集中在绝缘层的破坏点。当直接雷击或感应雷击破坏了绝缘导线的绝缘层后,其电弧电流就能导致相间短路,由于电弧部位被固定,绝缘导线发生雷击后比裸导线更容易断线。此外线路上的绝缘子也会因雷击而发生闪络或爆裂,甚至造成导线熔断等事故。
2.2 绝缘进水、导线氧化
绝缘导线在施工过程中,线路终端、接口及“T”接处的切口处,绝缘层未做绝缘处理或绝缘处理不当,水通过毛细管的吸泓作用进入铝导线内,并结聚在弧垂的低处。由于环境污染等因素,特别是在化工区域的雨水带有酸性,与铝产生氧化反应生成白色粉末,这类氧化物在电场的作用下加速对导线的腐蚀,使导线强度降低,出现绝缘层膨胀现象,甚至发生断线,缩短了导线寿命。
2.3 材料选型方面的问题
绝缘导线在附属材料选型中,没有严格按照绝缘导线的使用要求,为了减少资金投入而选用裸导线架空配套使用的相关材料来代替,严重影响绝缘导线的安全使用性能,加快了导线绝缘层的老化和铝导线的氧化腐蚀。
非承力接头如跳线、“T”接线、导线与设备的连接处,大量使用绝缘穿刺线夹,穿刺线夹虽然施工方便,但在应用过程中损伤了绝缘导线的绝缘层,同时线夹又伤及到内部导线,若线夹安装方式不当导致线夹与导线接触不良发热、或绝缘护罩处理不当使雨水进入绝缘导线,导致导线腐蚀等,均会使导线发生断线故障。
2.3 施工工艺方面的问题
2.3.1 在导线的放线、紧线过程中未按照规程规定的要求选用滑轮,导致导线绝缘层损伤甚至造成紧线时发生断线故障。
2.3.2 接地环安装在耐张线夹的受力侧导线上,由于绝缘层的收缩作用,剥离长度是要变化的,绝缘、防水的措施很可能被破坏,且剥去绝缘层,机械强度下降,受导线振动影响,该点的导线疲劳,容易断线。
2.3.3 绝缘线与绝缘子接触部分没有缠绕绝缘自粘带。导线与绝缘子固定扎线使用金属裸线,运行中产生放电烧坏绝缘层。
以上几种只是在绝缘线的安装、运行中少数不规则施工方法,由于受架空裸线安装工艺和方法的影响,存在许多不当之处,造成进水、导线从线夹中滑出、导线振动疲劳、局部发热等,影响绝缘线的安全运行,缩短使用寿命。
3 应对措施
3.1 强化中压线路的防雷措施
以上原因说明架空绝缘导线容易引起雷击断线故障,因此在电网建设改造过程中,无论是新建线路还是改造线路,都必须重视架空绝缘线路的防雷措施,如安装避雷器、保护间隙等。
3.1.1 氧化锌避雷器的防雷措施
避雷器是通过泄放雷电流,限制配电线路的感应过电压,达到保护的目的。其过电压保护性能良好,广泛应用于电气线路(设备)的过电压保护,由于避雷器有效保护距离是有限的,所以在全线架空绝缘线路上,安装避雷器存在着安装密度问题。
在《架空绝缘配电线路設计规程》中明确表示:应对雷击危害,架空绝缘线路上安装避雷器,重雷区应每隔150米安装一组来提高架空绝缘线路的防雷能力。实践表明,避雷器的安装密度增加,线路感应过电压的事故下降。若线路的每基杆塔均安装避雷器,安装避雷器和加装接地装置需要投入大量资金,运行维护工作量也很大,且避雷器故障和预防性试验将引起线路停电,即不经济又不可靠。
根据国外专家研究认为,单纯限制雷电感应过电压事故,每组避雷器的安装密度为200~360m。在濮阳城区与郊区绝缘架空配电线路中一般每隔300米安装一组避雷器。
3.1.2 保护间隙的防雷措施
保护间隙,又称放电间隙。这是一种简单的过电压保护措施。在正常情况下,带电部分与大地被间隙隔开,当线路落雷时,间隙被击穿后,雷电流被泄入大地,即在绝缘线上引出带电导体,一般采用圆形或棒形两种,圆形的钢弯曲成环和两环相网络,保持一定差距,环绝缘体可以串成均衡的效果,棒性材料可用两个圆形材料造成棒形电极,两个电极保持一定的距离,而且在最上一栏安装两个金属电极形成一球电极间隙,以避免烫伤,在18~21.06mm可以有效地满足保护间隙的效要求。
保护间隙在中性点不接地系统中,单相保护间隙动作,流过保护间隙的是线路的电容电流,在电弧电流过零时,空气介质恢复强度,电弧熄灭;两相或三相保护间隙同时发生闪络动作,流过保护间隙为工频续流的短路电流,所以,保护间隙是不能切断雷电电流之后的工频短路电流,只能靠断路器保护动作切断电源,恢复保护间隙的绝缘强度,用重合闸配合送电。由于放电间隙动作电压较高,截波时对电气设备严重威胁;实践情况表明,动作放电时会烧坏间隙的电极和附近设备,但能降低断线故障,比较经济。因此,可以选择在耐张杆上安装。
3.1.3 架空地线或耦合地线的防雷措施
在架空线路上安装架空地线或耦合地线,主要是将幅值很大的雷电过电压转化为电流,经很低的杆塔接地电阻排泄出去,从而大幅度降低雷电过电压,是导线得到保护。但配电线路前线架设地线,但可行性和难度大,成本高,不宜采取。
3.2 增强施工工艺水平
3.2.1 绝缘导线的架设中选择气温干燥的天气进行,放线、紧线时要选用塑料滑轮或套有橡胶护套的铝滑轮。滑轮直径不应小于绝缘线外径的12倍,槽深不小于绝缘线外径1.25倍,槽底部半径不小于0.75倍绝缘线外径,轮槽槽倾角为15 ℃。绝缘线允许弯曲半径大于20倍的绝缘线外径。导线不得在地面、杆塔、横担、瓷瓶或其他物体上拖拉,以免损伤导线绝缘层。
3.2.2 架空绝缘导线的绝缘层损伤后,线芯截面损伤不超过导电部分截面的17%时,可敷线修补,敷线长度应超过损伤部分,每段缠绕长度超过损伤部分不小于100mm。损伤程度在绝缘层厚度的10%及以上时必须进行绝缘补强补强处理,可用绝缘自粘胶带缠绕修补,也可用专用的绝缘护罩将导线的绝缘层损伤部位罩好,并将绝缘胶带将开口部位用自粘胶带缠绕封好。在同一档距内,单根绝缘导线绝缘层的修补部不宜超过3处。
3.2.3 绝缘线的连接用采用专用的线夹、接续管连接,不同金属、不同规格、不同绞向的绝缘线严禁在档内做承力连接。在剥离导线的绝缘层或半导体层时应使用专用的切削工具,不得损伤导线,剥口处绝缘层与线芯称45º夹角。所有绝缘线的接点终头、接头和绝缘线的切口处必须进行绝缘封护,不得有导线、接头裸露,防止进水。
3.2.4 非承力接头包括跳线、T接线、导线与设备的连接必须使用接续线夹,并安装专用绝艳护罩,绝缘护罩不得磨损、划伤,安装位置不得颠倒,有引线时一律向下,需要紧固部位应牢固严密,两端口需绑扎的必须用绝缘自粘带绑扎两层以上。
3.2.5 中压绝缘线必须进行屏蔽处理,绝缘线接头处的线夹、接续管的型号与导线规格匹配;压缩连接接头的电阻不应大于导线电阻的1.2倍,机械强度不应小于导体计算拉断力的90%;导线接头紧密、牢靠、选型美观,不应有重叠、弯曲、裂纹及凹凸现象。
3.2.6 承力接头的连接采用钳压法、液压法施工,在接头处安装辐射交联热收缩管护套或预扩张冷缩绝缘套管;绝缘护套管径一般应为被处理部位接续管的1.5~2.0倍,中压绝缘线使用内外两层绝缘护套进行绝缘处理;有导体屏蔽层的绝缘线的承力接头,应在接续管外面先缠绕一层半导体自粘带和绝缘线的半导体层连接后在进行绝缘处理,每圈半导体自粘带间搭压带宽的1/2;截面为240mm2及以上铝线芯绝缘线承力接头宜采用液压法施工。
3.2.7 绝缘线与绝缘子固定时,之间接触部分应用绝缘自粘带缠绕,缠绕长度应超出绑扎部位或与绝缘子接触部位两侧各30mm;没有绝缘衬垫的耐张线夹内的绝缘线宜剥去绝缘层,其长度和线夹等长,误差不大于5mm,将裸露的铝线芯缠绕铝包带,耐张线夹和悬式绝缘子的球头应安装专用绝缘护罩罩好。
4 結束语
架空绝缘导线较普通架空裸导线优点显著,使其应用价值越来越明显,近年来城市配电网与农网系统配电线路的绝缘化率显著增加。但是,若架空绝缘导线的附属材料选择不当和施工工艺不合理及防雷设施的不到位,不仅会加快绝缘导线绝缘层老化速度及铝导线的氧化反应,留下很多事故隐患,还会严重影响配电线路的安全运行。
【关键词】架空绝缘导线问题措施可靠
[Abstract] along with the further development of city and countryside construction, the line corridor became more and more nervous, overhead insulated conductor becomes one of the more commonly used wire city power grid construction, there are many problems to help guide line of bare existence, effectively improve the healthy water line level, enhance the reliability of power supply line. But due to defects in circuit design and construction technology, lead to the line has many fault in operation, affecting the stable operation of line. This paper discusses the system overhead insulated conductor prone to problems in the application, and to the problems discussed in the operation of the measures taken.
[keyword] overhead insulated conductor problem of reliable measures
中图分类号:TM245文献标识码:A 文章编号:2095-2104(2013)
1 前言
架空绝缘导线,又称架空绝缘电缆,随着社会经济的发展,架空绝缘导线是近几年在城网建设中发展起来的一种较新型线材,与普通架空裸导线相比,具有许多优点,可解决常规裸导线在运行过程中遇到的一些难题,价格又比地埋电缆造价便宜,因此,在城网与农网改造中广泛为人们所选用。但随着配电网的进一步发展和建设,线路建设越来越长。架空绝缘导线在雷雨季节时常发生雷击断线事故或导线进水氧化等事故隐患,使线路的健康水平大大降低,线路供电可靠性显著下降,提高配电线路运行检修人员的工作强度。
2 架空绝缘导线存在的问题
2.1 雷害事故多
根据濮阳郊区配网线路运行数据:2009年至2013年间,郊区配网线路共发生雷击14次,其中架空绝缘线路发生雷击9次,占郊区配电线路雷击故障的64.28%(郊区线路绝缘化率为11.89%)。因郊区配网使用架空绝缘导线时间较短,无论是新建线路还是改造线路,只考虑线路的绝缘化率的提高,与树线矛盾的问题,缺忽略了架空绝缘导线的防雷问题,对线路的安全运行造成一定的影响。
绝缘架空导线之所以容易遭受断线的原因是:当雷击绝缘导线时,绝缘导线的绝缘层会对雷电产生的电弧移动形成屏障,导致电弧移动速度较慢,使得工频电弧集中在绝缘层的破坏点。当直接雷击或感应雷击破坏了绝缘导线的绝缘层后,其电弧电流就能导致相间短路,由于电弧部位被固定,绝缘导线发生雷击后比裸导线更容易断线。此外线路上的绝缘子也会因雷击而发生闪络或爆裂,甚至造成导线熔断等事故。
2.2 绝缘进水、导线氧化
绝缘导线在施工过程中,线路终端、接口及“T”接处的切口处,绝缘层未做绝缘处理或绝缘处理不当,水通过毛细管的吸泓作用进入铝导线内,并结聚在弧垂的低处。由于环境污染等因素,特别是在化工区域的雨水带有酸性,与铝产生氧化反应生成白色粉末,这类氧化物在电场的作用下加速对导线的腐蚀,使导线强度降低,出现绝缘层膨胀现象,甚至发生断线,缩短了导线寿命。
2.3 材料选型方面的问题
绝缘导线在附属材料选型中,没有严格按照绝缘导线的使用要求,为了减少资金投入而选用裸导线架空配套使用的相关材料来代替,严重影响绝缘导线的安全使用性能,加快了导线绝缘层的老化和铝导线的氧化腐蚀。
非承力接头如跳线、“T”接线、导线与设备的连接处,大量使用绝缘穿刺线夹,穿刺线夹虽然施工方便,但在应用过程中损伤了绝缘导线的绝缘层,同时线夹又伤及到内部导线,若线夹安装方式不当导致线夹与导线接触不良发热、或绝缘护罩处理不当使雨水进入绝缘导线,导致导线腐蚀等,均会使导线发生断线故障。
2.3 施工工艺方面的问题
2.3.1 在导线的放线、紧线过程中未按照规程规定的要求选用滑轮,导致导线绝缘层损伤甚至造成紧线时发生断线故障。
2.3.2 接地环安装在耐张线夹的受力侧导线上,由于绝缘层的收缩作用,剥离长度是要变化的,绝缘、防水的措施很可能被破坏,且剥去绝缘层,机械强度下降,受导线振动影响,该点的导线疲劳,容易断线。
2.3.3 绝缘线与绝缘子接触部分没有缠绕绝缘自粘带。导线与绝缘子固定扎线使用金属裸线,运行中产生放电烧坏绝缘层。
以上几种只是在绝缘线的安装、运行中少数不规则施工方法,由于受架空裸线安装工艺和方法的影响,存在许多不当之处,造成进水、导线从线夹中滑出、导线振动疲劳、局部发热等,影响绝缘线的安全运行,缩短使用寿命。
3 应对措施
3.1 强化中压线路的防雷措施
以上原因说明架空绝缘导线容易引起雷击断线故障,因此在电网建设改造过程中,无论是新建线路还是改造线路,都必须重视架空绝缘线路的防雷措施,如安装避雷器、保护间隙等。
3.1.1 氧化锌避雷器的防雷措施
避雷器是通过泄放雷电流,限制配电线路的感应过电压,达到保护的目的。其过电压保护性能良好,广泛应用于电气线路(设备)的过电压保护,由于避雷器有效保护距离是有限的,所以在全线架空绝缘线路上,安装避雷器存在着安装密度问题。
在《架空绝缘配电线路設计规程》中明确表示:应对雷击危害,架空绝缘线路上安装避雷器,重雷区应每隔150米安装一组来提高架空绝缘线路的防雷能力。实践表明,避雷器的安装密度增加,线路感应过电压的事故下降。若线路的每基杆塔均安装避雷器,安装避雷器和加装接地装置需要投入大量资金,运行维护工作量也很大,且避雷器故障和预防性试验将引起线路停电,即不经济又不可靠。
根据国外专家研究认为,单纯限制雷电感应过电压事故,每组避雷器的安装密度为200~360m。在濮阳城区与郊区绝缘架空配电线路中一般每隔300米安装一组避雷器。
3.1.2 保护间隙的防雷措施
保护间隙,又称放电间隙。这是一种简单的过电压保护措施。在正常情况下,带电部分与大地被间隙隔开,当线路落雷时,间隙被击穿后,雷电流被泄入大地,即在绝缘线上引出带电导体,一般采用圆形或棒形两种,圆形的钢弯曲成环和两环相网络,保持一定差距,环绝缘体可以串成均衡的效果,棒性材料可用两个圆形材料造成棒形电极,两个电极保持一定的距离,而且在最上一栏安装两个金属电极形成一球电极间隙,以避免烫伤,在18~21.06mm可以有效地满足保护间隙的效要求。
保护间隙在中性点不接地系统中,单相保护间隙动作,流过保护间隙的是线路的电容电流,在电弧电流过零时,空气介质恢复强度,电弧熄灭;两相或三相保护间隙同时发生闪络动作,流过保护间隙为工频续流的短路电流,所以,保护间隙是不能切断雷电电流之后的工频短路电流,只能靠断路器保护动作切断电源,恢复保护间隙的绝缘强度,用重合闸配合送电。由于放电间隙动作电压较高,截波时对电气设备严重威胁;实践情况表明,动作放电时会烧坏间隙的电极和附近设备,但能降低断线故障,比较经济。因此,可以选择在耐张杆上安装。
3.1.3 架空地线或耦合地线的防雷措施
在架空线路上安装架空地线或耦合地线,主要是将幅值很大的雷电过电压转化为电流,经很低的杆塔接地电阻排泄出去,从而大幅度降低雷电过电压,是导线得到保护。但配电线路前线架设地线,但可行性和难度大,成本高,不宜采取。
3.2 增强施工工艺水平
3.2.1 绝缘导线的架设中选择气温干燥的天气进行,放线、紧线时要选用塑料滑轮或套有橡胶护套的铝滑轮。滑轮直径不应小于绝缘线外径的12倍,槽深不小于绝缘线外径1.25倍,槽底部半径不小于0.75倍绝缘线外径,轮槽槽倾角为15 ℃。绝缘线允许弯曲半径大于20倍的绝缘线外径。导线不得在地面、杆塔、横担、瓷瓶或其他物体上拖拉,以免损伤导线绝缘层。
3.2.2 架空绝缘导线的绝缘层损伤后,线芯截面损伤不超过导电部分截面的17%时,可敷线修补,敷线长度应超过损伤部分,每段缠绕长度超过损伤部分不小于100mm。损伤程度在绝缘层厚度的10%及以上时必须进行绝缘补强补强处理,可用绝缘自粘胶带缠绕修补,也可用专用的绝缘护罩将导线的绝缘层损伤部位罩好,并将绝缘胶带将开口部位用自粘胶带缠绕封好。在同一档距内,单根绝缘导线绝缘层的修补部不宜超过3处。
3.2.3 绝缘线的连接用采用专用的线夹、接续管连接,不同金属、不同规格、不同绞向的绝缘线严禁在档内做承力连接。在剥离导线的绝缘层或半导体层时应使用专用的切削工具,不得损伤导线,剥口处绝缘层与线芯称45º夹角。所有绝缘线的接点终头、接头和绝缘线的切口处必须进行绝缘封护,不得有导线、接头裸露,防止进水。
3.2.4 非承力接头包括跳线、T接线、导线与设备的连接必须使用接续线夹,并安装专用绝艳护罩,绝缘护罩不得磨损、划伤,安装位置不得颠倒,有引线时一律向下,需要紧固部位应牢固严密,两端口需绑扎的必须用绝缘自粘带绑扎两层以上。
3.2.5 中压绝缘线必须进行屏蔽处理,绝缘线接头处的线夹、接续管的型号与导线规格匹配;压缩连接接头的电阻不应大于导线电阻的1.2倍,机械强度不应小于导体计算拉断力的90%;导线接头紧密、牢靠、选型美观,不应有重叠、弯曲、裂纹及凹凸现象。
3.2.6 承力接头的连接采用钳压法、液压法施工,在接头处安装辐射交联热收缩管护套或预扩张冷缩绝缘套管;绝缘护套管径一般应为被处理部位接续管的1.5~2.0倍,中压绝缘线使用内外两层绝缘护套进行绝缘处理;有导体屏蔽层的绝缘线的承力接头,应在接续管外面先缠绕一层半导体自粘带和绝缘线的半导体层连接后在进行绝缘处理,每圈半导体自粘带间搭压带宽的1/2;截面为240mm2及以上铝线芯绝缘线承力接头宜采用液压法施工。
3.2.7 绝缘线与绝缘子固定时,之间接触部分应用绝缘自粘带缠绕,缠绕长度应超出绑扎部位或与绝缘子接触部位两侧各30mm;没有绝缘衬垫的耐张线夹内的绝缘线宜剥去绝缘层,其长度和线夹等长,误差不大于5mm,将裸露的铝线芯缠绕铝包带,耐张线夹和悬式绝缘子的球头应安装专用绝缘护罩罩好。
4 結束语
架空绝缘导线较普通架空裸导线优点显著,使其应用价值越来越明显,近年来城市配电网与农网系统配电线路的绝缘化率显著增加。但是,若架空绝缘导线的附属材料选择不当和施工工艺不合理及防雷设施的不到位,不仅会加快绝缘导线绝缘层老化速度及铝导线的氧化反应,留下很多事故隐患,还会严重影响配电线路的安全运行。