1992年11月1日19时30分,我市某单位一台KZL 4-13-A型锅炉发生爆管。经检查发现,该炉左集箱第11根水汽壁管中下部靠炉膛一侧过热变形鼓疱并爆破,鼓疱长度460mm,破口处其环向裂口长30mm、纵向裂口长8mm。管子减薄并呈兰色。割管后发现φ63.5×4mm管子已被水垢堵死;其相邻两根管也轻度变形;左集箱垢片、铁锈等沉渣大量堆积,其厚度约60mm;其他水冷壁管被水垢堵塞35根,占全部水冷壁管的47%,锅内各部位水垢厚2-2.5mm。造成事故的直接原因是水汽壁管被水垢堵塞过热爆破。该单位虽有水处理设备但管理不善、效果差,锅炉给水水质长期不符合国家标准,以致积垢严重,引发
At 19:30 on November 1, 1992, a KZL 4-13-A boiler exploded by a unit in our city. The inspection found that the furnace left header eleventh water vapor tube in the lower part of the middle of the furnace by the side of the bulge and overheating deformation blasting, bulge length 460mm, breaking the ring at the crack length of 30mm, longitudinal crack length 8mm. The tube is thin and blue. After the pipe was found φ63.5 × 4mm pipe has been blocked by scale; the two adjacent tubes also mild deformation; left set of box tablets, rust and other sediment accumulation a large number of its thickness of about 60mm; Blockage of 35, accounting for 47% of all water wall tubes, the various parts of the scale thick 2-2.5mm. The direct cause of the accident is the water pipe wall was overheated blasting blockage. Although the unit of water treatment equipment, but poor management, the effect is poor, long-term boiler water quality does not meet national standards, resulting in serious scale deposition, triggering