论文部分内容阅读
The present work is focused on heat and mass transfer in a direct evaporative air cooler of one row counter flow spray. Models of the two-phase flow in such a air treatment system have been developed. The fields of temperature and relative humidity in spray chamber, as well as the trajectories of sprayed drops have been obtained by numerical method. Experiments aiming at quantifying the system performance and its influence factors have been conducted. It indicates that the increase of air velocity and water/air ratio while the decrease of nozzle density are favorable. The performance of the system of parallel flow spray and counter flow spray have been compared by means of humidifying efficiency. Comparison between numerical simulation and experimental results demonstrate good agreement for outlet air temperature with a maximum error of 8% observed for air relative humidity.